AC800M Firmware Upgrade 1.download of controller firmware via Serial line connect the serial RS-232 tool cable between the Control Builder M node And the tool port of the controller Controller Tool Port AC800M COM4 Connector RJ45 Cable Name TK212 or TK212A Selctor the appropriate COM port for the Control Builder M node (default COM1 Power up the controller Select:Start All ProgramsABB Industrial IT 800xAEnginneringUtilitiesSerial Firmware Upgrade Select Settings from the dialog ,followed by the COM port selected for the Control Builder M node Click Connect Hold down the Init/Reset button on the controller for at least 3 seconds until the green R LED starts to blink Release the Init/Reset button and the controller will perform a cold test .Wait about a minute until a message appears a. If the connection is correct,then the Serial Firmware Upgrade dialog appears as shown in Figure below Serial

Firmware Dialog
Firmware Upgrade State Firmware Version Connected PM860 FW856/860 0.43.9.5 2000-10-03 Process

Connect
Upgrade Exit Com1 9600 No Connection b. If the Connect faile error message appears,check the cables and repeat the steps thus far in this procedure(refer to the Serial Firmware Upgrade Online Help. 9.Select the firmware version in the Firmware version drop-down list box. 10.Click Upgrade and wait five to ten minutes.The LED behavior during the upgrade procedure is described in the Serial Firmware Upgrade Online Help 11.Hold down the Init/Reset button on the controller for atleast three seconds.For redundant controllers,repeat

this procedure for both CPUS. 12.Before checking the firmware download,or connecting an AC 800M Controller to a Control Network,its IP address must be set. Setting the IP Address for AC 800M Controllers 1. Connect the serial RS-232 tool cable between the Control Builder M node and the tool port of the controller 2. Select the appropriate COM port for the CBM node (default COM1. 3. Select: Start All ProgramsABB Industrial IT 800xAEnginneringUtilitiesIPConfig 4. In the IP Config dialog,select:SettingsAdvanced mode 5.
Click Connect 6. Hold down the Init/Reset button on the controller for at least three seconds and wait up to one minute 7. Enter a unique Primary Ethernet Interface IP Address and Subnet mask according to the planning and preparation topic in industrial IT ,800XA-System, 8. Click Set IP in the IPConfig dialog to send the new address to the controller .

9. Restart controller ,for example with the Init/Reset button.


免费下载 Word文档免费下载: AC800M固件更新_COM-

  • 29.8

    ¥45 每天只需1.0元
    1个月 推荐
  • 9.9

    ¥15
    1天
  • 59.8

    ¥90
    3个月

选择支付方式

  • 微信付款
郑重提醒:支付后,系统自动为您完成注册

请使用微信扫码支付(元)

订单号:
支付后,系统自动为您完成注册
遇到问题请联系 在线客服

常用手机号:
用于找回密码
图片验证码:
看不清?点击更换
短信验证码:
新密码:
 
绑定后可用手机号登录
请不要关闭本页面,支付完成后请点击【支付完成】按钮
遇到问题请联系 在线客服